Part Number: ETI0001-2239
Rugged Mil Spec® 2000 VA
Rackmount Global UPS
US Navy / TAC-4 Standard
Product
W1 Configuration, Military
Power® Isolated
Mil Spec UPS
2000 VA Rugged Rack Mount, Modular Power System
Accepts 85-270 VAC, 46-440 Hz Input
Plus a Hot Swappable Battery Module
ETI0001-2239 Rugged UPS Standard Front Panel Layout
ETI0001-2239 Rugged UPS Standard Rear Panel Layout
The field proven
Military Power UPS line is ideally suited for military,
industrial, computer and telecommunications applications requiring high reliability, rugged construction, compact size and light weight design.
These units are equally suited for use in shipboard, airborne, vehicular, field
deployed or fixed locations with controlled or uncontrolled environments.
The ETI0001-2239 is specifically designed for lightweight
global power deployment or equally well in shallow depth racks including TAC-4 racks and
interfacing with either the TAC-4 PDU or any of numerous ETI
PDUs.
The heavy-duty chassis occupies only 7" (4U) of rack space while
delivering up to 2000 VA of clean, uninterruptible power. The rounded metal corners and rugged handles, aid
in safe handling. Internally, all major components are well secured and electrically
insulated to prevent damage due to shock and vibration. The optional heavy-duty rack slides provide
easy installation and removal of the unit with full extension. Rear shock
isolation/alignment bushings off load the slides when the unit is fully engaged.
The internal shielded
input transformer provides galvanic isolation with provisions for
both domestic (115
VAC, CONUS) and international (230 VAC, OCONUS) input
voltages. The autoranging input voltage selection allows inputting either 115 VAC or 230 VAC
without having to open the UPS enclosure.
Special EMI/RFI filters and input
power factor correction minimize both input current and harmonics. The input
switch and the galvanic isolation transformer provide a double pole isolated source for all installations including shipboard systems or
overseas locations where phase references and grounding are not consistent.
The LED arrays keep the operator informed as to
the unit's status including load and battery levels. The high intensity audible alarm can
be heard in high noise environments.
All controls and protective devices are brought to front and rear panels with critical
switches having finger guards. Further, all front panel devices are recessed to prevent
damage or accidental operation.
The rear panel provides locking
connectors for the input and output power with various optional configurations
available. This reverse air flow version draws air through the front and exhausts out the rear
vent into the rack. A removable and washable intake air filter and high capacity
stainless steel ball
bearing fan provide added protection in both controlled and hostile environments.
The batteries are maintenance free with immobilized electrolyte and are
constructed of flame retardant materials. The ETI0001-2239 has the added benefit of
having a front drawout hot-swappable battery module. For more information, see the
Battery
Technology section. The two
status D shell connectors provide both a contact and serial interface with
optional computer software providing loss of AC and low battery status as well as remote shut down
capability.
See the Power Distribution Units section for a listing of
stand alone PDUs. See the N5 Series ETI0001-1482 for a
version of this UPS with an integrated PDU and remote control
Overall, the Military
Power line is uniquely
qualified for critical shipboard, vehicle, airborne or land based systems combining
advanced modular design features with highly reliable construction.
Technical Specifications:
P/N: ETI0001-2239
AC OUTPUT |
Output voltage: |
120 VAC true sinewave std, up to 600 VAC
optional |
Output rating: UPS |
2000 VA, standard in 4U x 21" chassis
0.65-0.75 pf std, optional configurations to 24,000 VA |
Non-linear load capacity: |
Up to 100% non-linear load capability w/o
derating |
Output voltage regulation: UPS |
± 3.0% static regulation of nominal
± 4.0% dynamic (0 to 50% load step) |
Overload surge capacity: |
110% for 10 minutes; 125% for 30 seconds |
Harmonic distortion: |
Less than 5.0% into 100% non-linear load |
Output frequency: UPS |
60 Hz ± 1.0% independent of input frequency
50,
400 or 1000 Hz output available as an option |
Operational status |
Status, load and battery (16) LEDs, w/contacts
RS-232 asynchronous serial status COM port
Adjustable level,+90 dB audible alarm w/on/off |
AC INPUT |
Input voltage selection: |
Autoranging from nominal 115 VAC to 230 VAC |
Input voltage tolerance: UPS |
+15% -25%, or 85-135 and 170-270 |
Input frequency: |
From 46 Hz to 440 Hz |
Input power factor: |
Better than 99% typically |
Input/output isolation: |
2000 VA, >120 dB common mode, <1.0
mA leakage |
Input transient suppression: |
Complies with IEEE 587 and UL 1449 |
Input control/protection: |
Guarded 2 pole switch (S1) w/fuse (F2) |
Input power connection: |
MS 3102A-22-2P, 3 pin, locking |
DC INTERNAL BATTERY |
Internal battery type: |
Maintenance free immobilized electrolyte,
Flame retardant materials (Oxygen Index 28+) |
Internal battery life: |
Rated for continuous service life of 5 years |
Internal battery protection: |
Rear panel mounted fuse (F1) |
Internal battery time: |
10+ minutes @ 1000 watt load, 20+ minutes @
50% |
Internal battery recharge: |
Recharged to nominal in <8 hours |
Internal battery replacement: |
Drawout/plug-in module from front of unit |
DISTRIBUTION PANEL |
Output circuits: |
One output standard, optional configurations |
Output control: |
Guarded 3 pole switch (S5) |
Output receptacles: |
MS 3102A-24-10S, 7 pin locking, other options |
MECHANICAL |
Dimensions ( H x D x W ): |
7.00 (4U) x20.9 x 19.0 in (178
x 531 x 483 mm) |
Rack Slide Mount Patterns: |
Jonathan, General Devices, others optional |
Alternate Mounting Options: |
Table, Wall, Floor, Portable,
Horizontal/Vertical |
Unit weight: |
98 lb. (45 kg) with lift handles front and
rear |
Audible noise: |
Less than 47 dB @ 5.0 ft., ANSI "A"
scale |
Cooling type: |
High capacity, negative pressure, forced air |
Cooling air direction: |
Front intake, exhaust to rear |
Air intake filter: |
Washable metal filter media, others optional |
ENVIRONMENTAL |
Storage temperature: |
-13° to 140° F ambient (-25° to 60° C) |
Operating temperature: |
50° to 104° F ambient ( 10° to 40° C) |
Operating humidity: |
0 to 95% relative humidity (non-condensing) |
Storage elevation: |
Up to 40,000 ft (12,192 m) |
Operating elevation: |
Up to 15,000 ft (4,572 m), higher optionally |
STANDARDS |
United States: |
Meets UL-1778 standard for UPS
equipment,
MIL STDs 167-1, 454, 810, 901D Grade A, 1399-300A & 2000
|
Canada: |
CSA C22.2 No. 107 UPS safety requirements |
EMI Protection: |
EMI/RFI FCC, Class A; EN55022; MIL
STD 461 standard |
OPTIONAL ACCESSORIES |
|
Autoranging International Input,
Emergency Power Off, Elapsed Time Meter, Cold Start, Alternate I/O Configurations, Dual Source
Input, Battery Expansion, Batteryless Operation, Battery
Charger/Conditioner, Power Distribution Units, Software
Interface, 10BaseT Ethernet SNMP/HTTP port,
Transport Cases |
This page was last modified on:
March 18, 2012
|